Power Factor Correction Calculator

This power factor correction calculator finds the capacitor kVAR needed to raise a load from its present power factor to a target, such as from 0.70 to 0.95. Enter the real power in kW and both power factors, and the power factor correction calculator returns the kVAR, the kVA before and after, the current reduction, and the capacitance in microfarads.

kW
V

Results

Enter your values and press Calculate to see results.

The Power Factor Correction Calculator is part of our AC & Three Phase collection. Browse more ac & three phase to size, convert, and check your work alongside this tool.

What the power factor correction calculator does

Motors and transformers draw reactive power to build their magnetic fields. That current does no useful work but still loads cables and transformers, and utilities often bill for it. Capacitors supply reactive power locally, so the supply delivers less. The power factor correction calculator works out how many kVAR of capacitors cancel enough reactive power to reach your target power factor.

kVAR = kW × (tan φ1 − tan φ2)

Power factor correction formula

The angle φ is the arccosine of the power factor:

kVAR = kW × (tan(acos PF1) − tan(acos PF2))
C (per phase, delta) = kVAR × 1000 ÷ (3 × 2π f V²)

The kVA after correction is kW ÷ PF2, and line current falls in the ratio PF1 ÷ PF2.

Power factor correction calculator example

A 100 kW load at 0.70 power factor, corrected to 0.95 on a 480 V, 60 Hz, three phase system:

kVAR = 100 × (1.020 − 0.329) = 69.15 kVAR
kVA falls from 142.86 to 105.26, current by 26.3%

The capacitance is 265.4 µF per phase in delta. A 250 kW plant at 0.80 corrected to 0.95 on 400 V, 50 Hz needs 105.33 kVAR.

How to use the power factor correction calculator

Enter the real power of the load in kW, from a power meter or your utility bill demand. Enter the present power factor and the target, often 0.95. Choose single or three phase, the line voltage, and the frequency if you want the capacitance in microfarads. Press Calculate to read the capacitor kVAR and the savings in kVA and current.

Reading the kVAR calculator result

Pick the next standard capacitor bank size at or slightly below the result, since overcorrection pushes the power factor leading and can raise voltage at light load. The current reduction shows how much capacity you free in cables and transformers. For loads that change through the day, an automatic bank switches steps in and out; fixed capacitors suit steady loads such as large motors that run all shift.

When to use a kVAR calculator

  • Avoiding utility penalties for low power factor
  • Freeing transformer capacity for new load
  • Sizing capacitors at a large induction motor
  • Cutting cable losses on long feeders
  • Planning an automatic capacitor bank

Common power factor correction mistakes

  • Overcorrecting. A leading power factor at light load raises voltage.
  • Ignoring harmonics. Drives can resonate with plain capacitors.
  • Sizing from one reading. Use demand data across the day.
  • Oversizing motor capacitors. Keep them below the motor magnetizing kVAR.

Tips for capacitor bank sizing

  • Target 0.95 rather than 1.0.
  • Use automatic steps for loads that vary.
  • Check capacitor voltage ratings against the system voltage plus margin.

Capacitor bank sizing in practice

Start from real data. A month of demand readings shows the kW and power factor at peak and at light load. Size the fixed part of the bank for the base load and let automatic steps follow the rest, so the power factor stays near target without going leading. Capacitors at individual motors correct the problem at its source and cut losses all the way back to the supply, but they must not exceed the motor magnetizing kVAR, or the motor can self excite when switched off. Variable speed drives and other nonlinear loads create harmonics that can resonate with capacitors, so plants with many drives use detuned banks with series reactors. Measure the existing power factor first with the power factor calculator.

Power factor correction and freed capacity

Correction shrinks the kVA a transformer must supply. In the example, 100 kW at 0.70 needs 142.86 kVA, but at 0.95 only 105.26 kVA, freeing about 37 kVA of transformer capacity and cutting current by 26%. Because cable losses scale with current squared, losses fall by about 45%. That headroom often lets a plant add machines without a new transformer. Check the new current per phase with the three phase power calculator.

Power factor correction multiplier table

Multiply the kW by this factor to get the capacitor kVAR:

Present PFTo 0.90To 0.95To 0.98To 1.00
0.600.8491.0051.1301.333
0.700.5360.6920.8171.020
0.750.3980.5530.6790.882
0.800.2660.4210.5470.750
0.850.1350.2910.4170.620
0.900.0000.1560.2810.484

Power Factor Correction Calculator FAQ

How do you calculate kVAR for power factor correction?

Multiply the kW by tan(acos PF1) minus tan(acos PF2). For 100 kW from 0.70 to 0.95 the factor is 0.692, so you need 69.15 kVAR.

What power factor should I target?

Most sites aim for 0.95. Many utilities penalize power factor below about 0.90, and going to 1.0 risks overcorrection when load drops.

How do I convert kVAR to microfarads?

For three phase delta, C = kVAR × 1000 ÷ (3 × 2πf × V²). The calculator shows the result in µF when you enter the voltage.

Do capacitors save energy?

They cut reactive current, which lowers losses in cables and transformers and can remove utility penalties, but they do not reduce the real kW the load uses.

Related Calculators