Chiller Tonnage Calculator

This chiller tonnage calculator sizes a chiller from the chilled water flow and temperature drop, or from a process load. Enter the flow in gpm or m³/h with the inlet and outlet temperatures, or the product mass flow, specific heat, and cooling range, and the chiller tonnage calculator returns the cooling load in tons, kW, and BTU/h and the chiller size with your safety margin.

%

Results

Enter your values and press Calculate to see results.

The Chiller Tonnage Calculator is part of our Cooling & Heating collection. Browse more cooling & heating to size, convert, and check your work alongside this tool.

What the chiller tonnage calculator does

A chiller removes heat from a fluid loop or a process, and its size is quoted in tons of refrigeration, where one ton removes 12,000 BTU per hour or 3.517 kW. The chiller tonnage calculator finds the heat to remove from the flow and temperature drop of the chilled fluid, or from the mass flow, specific heat, and cooling range of a product, then adds a safety margin to give the chiller size to select.

Chiller tonnage formula

The cooling load is the mass flow times the specific heat times the temperature difference:

Q (kW) = flow (m³/h) × ρ × 1000 ÷ 3600 × cp × ΔT
Tons = Q (kW) ÷ 3.517 = Q (BTU/h) ÷ 12,000

For water in US units this reduces to the familiar rule:

Tons = gpm × ΔT (°F) ÷ 24

Glycol mixes have a lower specific heat, so the calculator uses their own density and specific heat. The chiller size is the load times (1 + safety margin).

Chiller tonnage example

A chilled water loop circulates 50 gpm and the water returns at 55 °F and leaves the chiller at 45 °F:

Tons = 50 × 10 ÷ 24 = 20.83 tons

With the exact water properties the load is 20.88 tons, 73.4 kW, or 250,554 BTU/h. Adding a 20% safety margin gives a 25.1 ton (88.1 kW) chiller.

How to use the chiller size calculator

Choose US or metric units and the calculation. For a chilled water loop, choose the fluid, then enter the flow and the temperatures going into and out of the chiller evaporator. For a process chiller, choose the process option and enter the product mass flow, its specific heat, and the temperatures it must cool from and to. Set the safety margin, often 10 to 20%. Press Calculate.

Reading the chiller capacity calculation

The required chiller size is the nominal capacity to look for at your leaving water temperature. Chiller ratings are usually quoted at 44 or 45 °F leaving water and a set condenser condition; colder water, glycol, high ambient temperature, or altitude reduce the real capacity, so check the manufacturer derating tables. A margin that is too large wastes money and makes the chiller cycle on and off at low load.

When to use chiller sizing

  • Process chiller sizing for plastics molding, food, and laser cooling
  • Checking chiller tons for a building chilled water loop
  • Converting gpm to tons from a measured flow and temperatures
  • Sizing a glycol chiller for low temperature work
  • Comparing chiller capacity in kW and tons of refrigeration

Common chiller sizing mistakes

  • Using the pump flow but a wrong delta T. Measure both temperatures at the chiller.
  • Ignoring glycol. It lowers capacity at the same flow.
  • Oversizing heavily. A large margin causes short cycling.
  • Forgetting pump and piping heat. Add them to a process load.

Tips for chiller tonnage

  • Check the chiller rating at your leaving temperature and ambient.
  • Use a buffer tank on small loops to reduce cycling.
  • Log flow and temperatures to confirm the real load.

Process chiller sizing from the product load

For machines, the heat often comes from the product rather than from a known water flow. A molding machine that cools 2,000 lb/h of plastic, or a jacketed tank that cools a batch, sets the load through mass flow, specific heat, and temperature range. Add the heat of the pump, the piping gains, and any heat from hydraulics. When the load comes from a room or building rather than a process, the heat load calculator and the AC tonnage calculator are the better starting points.

Chilled water flow and the temperature difference

For a given load, a larger temperature difference means less flow, smaller pipes, and less pump energy; a 10 °F (5.6 K) drop is the classic design value and 12 to 16 °F is common in newer plants. The flow for a chosen temperature drop follows from the same formula, which the hydronic flow rate calculator solves for pipe sizing in a heating or cooling loop.

Chiller tons from gpm at a 10 °F temperature drop

Water flowCooling loadLoad in kWRule of thumb (gpm × ΔT ÷ 24)
10 gpm4.18 tons14.7 kW4.17 tons
24 gpm10.02 tons35.2 kW10 tons
50 gpm20.88 tons73.4 kW20.83 tons
100 gpm41.76 tons146.9 kW41.67 tons
240 gpm100.22 tons352.5 kW100 tons
500 gpm208.8 tons734.3 kW208.33 tons

Chiller Tonnage Calculator FAQ

How do you calculate chiller tonnage?

For water, multiply the flow in gpm by the temperature drop in °F and divide by 24. In metric, kW = m³/h × 1.163 × ΔT, and tons = kW ÷ 3.517.

How many gpm per ton for a chiller?

At a 10 °F temperature drop, 2.4 gpm per ton. At 12 °F it is 2 gpm per ton.

How much safety margin should a chiller have?

10 to 20% is common for process chillers. Comfort systems sized from a detailed load calculation often need less.

Does glycol reduce chiller capacity?

Yes. Glycol has a lower specific heat and is pumped colder, so the same chiller removes less heat. Use the glycol option and the maker derating.